Plan Review Notes
Plan Review Notes For Permit 04071234
Permit Number 04071234
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A LOAD CALCULATION FOR
 THE EXISTING LOADS AS WELL AS THE NEW
 LOAD PER 215.5.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER110.9.
  
 3} THE PANEL MOUNTED ON THE NEW
 STRUCTURE MUST BE GROUNDED PER 250.32.
  
 4} THE DRYER IS SHOWN AS 5KW IN THE LOAD
 CALC, BUT SHOWN ON A 40 AMP BREAKER ON
 THE PANEL SCHEDULE, PLEASE CORRELATE.
  
 5} THE AIR HANDLER IS SHOWN AT 7500
 WATTS IN THE LOAD CALC BUT SHOWN ON A
 40 AMP BREAKER. THE AHU CIRCUIT MUST BE
 RATED @ 125% PER 424.22(E).
  
 6} THE ARCHITECT MUST PROVIDE A TITLE
 BLOCK ON THE PLAN PER 61G1-16.004, AND
 MUST DATE THE SEAL, SAME ART. FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026