| Notes |
| Date |
Text |
| 2004-08-04 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A LOAD CALCULATION FOR | | | THE EXISTING LOADS AS WELL AS THE NEW | | | LOAD PER 215.5. | | | | | | 2} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER110.9. | | | | | | 3} THE PANEL MOUNTED ON THE NEW | | | STRUCTURE MUST BE GROUNDED PER 250.32. | | | | | | 4} THE DRYER IS SHOWN AS 5KW IN THE LOAD | | | CALC, BUT SHOWN ON A 40 AMP BREAKER ON | | | THE PANEL SCHEDULE, PLEASE CORRELATE. | | | | | | 5} THE AIR HANDLER IS SHOWN AT 7500 | | | WATTS IN THE LOAD CALC BUT SHOWN ON A | | | 40 AMP BREAKER. THE AHU CIRCUIT MUST BE | | | RATED @ 125% PER 424.22(E). | | | | | | 6} THE ARCHITECT MUST PROVIDE A TITLE | | | BLOCK ON THE PLAN PER 61G1-16.004, AND | | | MUST DATE THE SEAL, SAME ART. FAC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|