| 2004-08-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04071209 |
| | ADD: 1601 BELVEDERE RD# 303 SOUTH |
| | CONT: NEW LINE CONSTRUCTION |
| | TEL: (954)648-0955 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) ARCHITECTURAL PLANS MISSING : |
| | 481.219(2) F.S.A CERTIFICATE OF |
| | AUTHORIZATION SHALL BE REQUIRED FOR A |
| | CORPORATION, PARTNERSHIP, OR PERSON |
| | PRACTICING UNDER A FICTITIOUS NAME, |
| | OFFERING ARCHITECTURAL SERVICES TO THE |
| | PUBLIC JOINTLY OR SEPARATELY. |
| | |
| | 3) SHEET A-1.2 SHOWS A NEW ENTRY DOOR AT |
| | THE ENTRY. PLANS DO NOT INDICATE DOOR |
| | RATING. NOTE NO MINIMUM BUILDING TYPE |
| | PROVIDED. IS THE BUILDING PROTECTED OR |
| | FIRE SPRINKLERED. |
| | |
| | 4) FL BLD CODE 2405.2 HAZARDOUS LOCATION |
| | PROVIDE SAFETY GLASS FOR THIS LOCATION: |
| | GLASS NEXT TO DOORWAYS & WALKWAYS. |
| | |
| | 5) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY. |
| | |
| | 6) SHEET A-2.1 DETAIL A BREAK ROOM |
| | CABINETRY & SINK TO COMPLY WITH: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 8) SHEET A-1.2 NOTE"H" INDICATES THE USE |
| | OF A PRE-FABRICATED COLUMN, PROVIDE ADD- |
| | ITIONAL INFORMATION. 803.4 FOAM PLASTIC |
| | TRIM SHALL NOT BE USED AS INTERIOR |
| | FINISHES. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |