| Plan Review Notes For Permit 04071198 |
| Permit Number |
04071198 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-08-03 00:00:00 | RISER DIAGRAM IS NOT CORRECT. | | | | | | 400 AMP METER MAIN CONBO WOULD NOT HAVE | | | A 60 AMP PANEL FOR POOL EQUIPMENT. | | | | | | PANEL A2 IS THE PANEL THAT WOULD FEED | | | PANELS B AND C AND THE POOL PANEL, OR | | | HAVE THE POOL EQUIPMENT BREAKERS WITH | | | THEM. | | | | | | RISER AND PANEL SCHEDULE SHOW 200 AND | | | 150 PANELS FOR A AND B WHICH IS IT. | | | | | | IF YOU SUBMIT THE SAME PLANS IN AGAIN IT | | | WILL HAVE TO GO TO BUILDING FOR PLAN | | | REVIEW ALSO UNLESS YOU TAKE OUT A3. | | | A3 HAS NO ELECTRIC ON IT. | | | | | | | | | QUESTIONS CALL JAKE644-7291 |
|