| 2005-07-26 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PANEL SCHEDULES SUBMITTED. |
| | PLEASE SEE PANEL "A2" ON RISER INDICATES |
| | BRKRS ETC TO 200A SUB PANELS, HOWEVER |
| | BRKR/OCP IS SHOWN FOR POOL PANEL FEED. |
| | PLEASE SEE PANEL SCHEDULE SUBMITTED FOR |
| | A2, SEEMS TO BE THE POOL PANEL, PANEL |
| | SCHEDULE?? |
| | PLEASE ALSO LABEL PLANS AND SHOW ALL |
| | PANELS AND/OR DISCONNECTS. |
| | PLEASE LABEL AND CORRELATE. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE 310.15B6 FOR MIN |
| | SEC'S TO BE SHOWN. PLEASE SEE 400A |
| | SERVICE IS SHOWN AND PROVIDED , HOWEVER |
| | ONLY ONE SET OF 3 2/0'S IS SHOWN FROM |
| | FPL HAND HOLE.? |
| | 240.4,310.15B6 ETC. |
| | |
| | 3)NOTE: PLEASE INDICATE OF ALL |
| | CONTINUOUS LOADS(POOL PUMP) IS SHOWN |
| | ALREADY @125%. |
| | 215.3,230.42 ETC. |
| | |
| | 4)NOTE: PLEASE SEE REDLINED PLANS FOR |
| | WHAT APPEARS TO BE A COUPLE OF MISSING |
| | RECEPTS REQUIRED UNDER 210.52. |
| | |
| | 5)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK PER FAC |
| | 61G1-16.004. PLEASE SEE MISSING PRINTED |
| | NAME AND LICENSE # FOR ARCHITECT OF |
| | RECORD. |
| | THIS IS REQUIRED OF ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |