| Date |
Text |
| 2004-08-02 00:00:00 | ************ UNSAT **************** |
| | |
| | 1 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE SEE NOTE MENTIONS TO WIRE SD'S |
| | AHEAD OF BATH/KIT LTS. ARC FAULT |
| | PROECTION WOULD ALSO BE REWUIRED FOR |
| | THOSE BRANCH CIRCUIT(S). |
| | |
| | 2 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 3)NOTE: PLEASE SEE RISER INDICATES |
| | EQUIPMENTS GRNDS FROM METER TO MAINS. |
| | PLEASE SEE 250.6 ,250.24 THIS IS NOT |
| | PERMITTED. EQUIPMENT GRNDS ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNETC. |
| | |
| | PLANS ARE COMING BACK FOR PLUMB COMMMENT |
| | -S PLEASE CORRECT. |
| | |
| | ONLY NOTE: FEEDERS FROM MAINS TO PANELS |
| | SHOWN AS 2/0'S WHICH ARE RATED FOR 200A' |
| | S. |
| | |
| | ONLY NOTE: PLEASE INLCUDE ANY OTHER LV |
| | ON PLANS.PRE-WIRE SOUND ETC. |
| | IF NOT ON PLANS, SEAPRATE PLANS AND |
| | PERMIT WILL BE REQUIRED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |