Plan Review Notes
Plan Review Notes For Permit 04071171
Permit Number 04071171
Review Stop B
Sequence Number 3
Notes
Date Text
2005-03-07 00:00:00DENIED
  
 1) SUBMIT COMPLETE TESTING REPORTS (WITH
 ANY LIMITATIONS) AND INSTALLATION
 INSTRUCTIONS AND DRAWINGS FOR THE
 ASPHALT ROOF SHINGLES. NOTE: STRUCTURE
 EXCEEDS 33 FEET.
  
 2) SUBMIT THE NOA OR EVALUATION REPORT
 FROM THE STATE PRODUCT APPROVAL WEBSITE
 FOR THE GLASS BLOCK. IT IS MISSING FROM
 THE SUBMITTAL.
  
 3) THE SIMPSON CONNECTOR SPECIFIED ON S4
 FOR MARK (J) IN THE SCHEDULE AS HDSA IS
 A TYPO AND SHOULD BE HD5A. PLEASE
 CORRECT.
  
 4) THE CONNECTOR SPECIFIED AT THE
 EXTERIOR WALL FOR THE MG1 GIRDER TRUSSES
 IS NOT ADEQUATE TO RESIST THE UPLIFT
 LISTED IN THE TRUSS DRAWINGS.
  
 5) PLEASE CLARIFY THAT DETAIL 10 ON S7
 IS TYPICAL FOR EACH END OF ALL THE GR2
 GIRDERS AND ONE END OF THE GR1 GIRDERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  