Plan Review Notes
Plan Review Notes For Permit 04071171
Permit Number 04071171
Review Stop B
Sequence Number 2
Notes
Date Text
2004-12-10 00:00:00DENIED
  
 1) THE OWNER/AGENT IS REQUIRED TIO SIGN
 THE ENERGY CALC. FORMS. THE ENERGY
 CALCS. DO NOT SPECIFY THE 2X6 WOOD FRAME
 EXTERIOR WALLS WITH R-19 INSULATION. THE
 PLANS SPECIFY R-30 CEILING INSULATION
 AND THE ENERGY CALCS. LISTS R-19. PLEASE
 CORRECT.
  
 2) FBC 2504.2.1 REQUIRES EXTERIOR
 APPLICATIONS OF PORTLAND CEMENT PLASTER
 TO COMPLY WITH ASTM C 926. THIS STANDARD
 REQUIRES PLASTER OVER METAL BASE TO BE
 5/8" THICK ON HORIZONTAL APPLICATIONS
 AND 7/8" FOR VERTICAL APPLICATIONS.
  
 3) MEAN ROOF HEIGHT FOR THE STRUCTURE IS
 38'-5". SUBMIT ENGINEERED CALCULATIONS
 FOR THE ROOF SHEATHING FASTENING
 REQUIREMENTS.
  
 4) PROVIDE CAP DETAILS FOR THE WOOD
 COLUMN (WP-1) AND THE STEEL COLUMN
 (SC-1).
  
 5) SECT.5 ON S7 WHICH SHOWS A 6X6 WD.
 POST, HOWEVER, NO ID TAG IS ON THE PLAN
 FOR THIS SECTION. PLEASE CLARIFY.
  
 6) SUBMIT PRODUCT APPROVALS FOR ASPHALT
 ROOF SHINGLES THAT WERE TESTED TO ASTM D
 3161 (MODIFIED TO 110 MPH) OR PA 107 AND
 ARE NOT LIMITED TO A 33'MRH.
  
 7) THE DOOR SCHEDULE FOR UNIT 2 & 2R
 DOES NOT LIST THE 16'WIDE OVERHEAD
 GARAGE DOOR OR THEIR REQUIRED DESIGN
 PRESSURES.
  
 8) THE NOA/EVALUATION REPORT FOR THE
 GLASS BLOCK IS MISSING.
  
 9) A PRODUCT APPROVAL FOR FIXED GLASS
 WINDOWS WAS SUBMITTED AND THERE AREN'T
 ANY SPECIFIED ON THE PLANS. PLEASE
 CLARIFY.
  
 10) THE TRUSS LAYOUTS AND DRAWINGS ARE
 REQUIRED TO HAVE THE ORIGINAL WET
 SIGNATURE OF THE TRUSS ENGINEER PER FAC
 61G15-23.002.
  
 NOTE: THE PRODUCT APPROVALS FOR THE
 6-UNIT "B" ELEVATION WERE USED FOR THIS
 REVIEW. SUBMIT COMPLETE SETS FOR EACH
 MASTER PERMIT.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714