2004-11-30 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE RECEPT ON 2' OF WALL
 IN BEDRM #2, APPEARS TO BE "IN" A WALL?
 210.52
  
 2)NOTE: IT HAS COME TO OUR ATTENTION
 THE
 SEC'S ARE ACTUALLY BEING INSTALLED BY
 THE ELECTRICAL CONTRACTOR AND NOT FPL>
 IF INDEED THIS WILL BE, THEN SEC'S ARE
 TO BE SHOWN ON RISER DIAGRAM AND MUST
 MEET 310.16 2002 NEC.
  
 3)NOTE: PLEASE ALSO SEE 250.66 FOR
 SIZING OF GROUNDING ELECTRODE
 CONDUCTOR.
 THIS MAY NEED TO BE CORRECTED ON RISER
 DUE TO SEC'S CHANGES?
 SHOWN AS 1/0 NOW, WHICH IS NOT LARGE
 ENOUGH.
 PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE TITLE BLOCKS FOR
 ELECTRICAL AND MECHANICAL SHEETS.
 THESE STILL INDICATE A "FIRM".
 PLEASE ADJUST TITLE BLOCK OR INCLUDE
 LICENSE # AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.023.
 PLEASE SEE THIS IS REQUIRED OF OTHER
 POSSIBLE SHEETS WHEATHER OR NOT COMMENT
 OS MADE BY OTHER REVIEWER(S).
  
 5)NOTE: PLEASE SEE PLANS STILL INDICATE
 A MAIN DISC AND 8-METERS. THIS COMMENT
 WAS GIVEN ONPREVIOUS REVIEW UNDER
 #04021360 THIS DOE NOT CORRELATE WITH
 RISER.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  