| Plan Review Notes For Permit 04071169 |
| Permit Number |
04071169 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-23 00:00:00 | DENIED | | | | | | 1) TRUSS CONNECTOR MARK 'J' ON SHEET S4 | | | CALLS FOR (2) HDSA. IS THIS SUPPOSE TO | | | BE A SIMPSON HD5A CONNECTOR? A TWO | | | MEMBER TRUSS IS SPECIFIED IN THE | | | CONNECTOR SCHEDULE AT THIS LOCATION, | | | HOWEVER IT IS A 4 MEMBER TRUSS. HOW WAS | | | THE UPLIFT DETERMINED FOR THESE | | | CONNECTORS. THE SIMPSON CATALOG LISTS A | | | TENSION LOAD OF 3980# FOR ONE CONNECTOR. | | | | | | 2) THE MG1 TRUSSES HAVE AN -1181# AT THE | | | EXTERIOR WALLS. THIS EXCEEDS THE | | | ALLOWABLE UPLIFT OF 990# OF THE SIMPSON | | | H10 CONNECTORS THAT ARE SPECIFIED. | | | | | | 3) THE GLASS BLOCK PRODUCT APPROVAL | | | SUBMITTAL IS MISSING THE MIAMI-DADE NOA | | | WITH THE INSTALLATION INSTRUCTIONS. | | | | | | 4) THE PRODUCT APPROVAL SUBMITTAL FOR | | | THE ASPHALT SINGLES IS MISSING THE | | | INSTALLATION INSTRUCTIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|