| Plan Review Notes For Permit 04071144 |
| Permit Number |
04071144 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-04 00:00:00 | FAILED: | | | 1. CIVIL SITE PLANS MUST BE REVIEWED AND | | | AND APPROVED FOR ALL THE CONNECTION TO | | | THE SREVICES, NO METER, DDCV FOR FIRE | | | LINE OR BACKFLOWS FOR DOMESTIC ARE SHOWN | | | SHEET 6 OF 10, NOTE THAT A SEPARATE | | | BACKFLOWS FOR EACH BUILDING PER PLUMBING | | | CODE IS REQUIRED. | | | 2. PLEASE PROVIDE STORM WATER CALC. FOR | | | OUR REVIEW AND APPROVAL, INCLUDE | | | PERVIOUS AND IMPERVIOUS AREA, BUILDING | | | AREA FOR THE ENITRE SITE. | | | 3. WORK IN PUBLIC R.O.W REQUIRES A | | | SEPARATE PERMIT FROM THE PUBLIC | | | UTILITIES AND ENGINEERING, WINDEL PALMER | | | 494-1086 AND FROM PB COUNTY WILL BE | | | REQUIRED. | | | 4. A SEPARATE PERMIT FOR SITE ELECTRICAL | | | WORK IS REQUIRED. | | | 5. LANDSCAPING PLAN MUST BE REVIEWED AND | | | APPROVED BY PLANNING AND ZONING, IT | | | SHOULD BE PART OF BUILDING PERMIT | | | APPLICATION SBMITTALS. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|