| Plan Review Notes For Permit 04071132 |
| Permit Number |
04071132 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-02-09 00:00:00 | PROVISO: | | | 1. RETURN AIR OUT OF MASTER BEDROOM | | | AREA REQUIRES 18" JUMPER. 2003 FBC/M | | | 601.4 EXCEPTION #1. | | | 2. AUX. DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED. 2001 FBC/M 307.2.3 | | | . | | | 3. PROVIDE FOR CONBUSTION AIR FOR DRYER | | | IF REQUIRED. | | | GAS DRYER INFORMATION NOT WITH PLAN | | | PACKAGE. | | | | | | PAT RAFTER 2/9/05 561/805/6728. |
|