| Plan Review Notes For Permit 04071122 |
| Permit Number |
04071122 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-03 00:00:00 | ********* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEERISER DIAGRAM HAS | | | BEEN REVISED TO INDICATE NO "POOL | | | PANEL", HOWEVER MAIN PANEL STILL SHOWS | | | POOL PANEL? | | | PLEASE CORRELATE.215.5 | | | | | | | | | 2)NOTE: PLEASE SEE REFERENCE TO 1999 NEC | | | FOR ARC FAULT PROTECTION. | | | 210.12 | | | | | | | | | 3)NOTE: PLEASE SEE PLANS DO NOT INDICATE | | | THE NEW "MAIN DISCONNECT" AS SHOWN ON | | | RISER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|