| Plan Review Notes For Permit 04071120 |
| Permit Number |
04071120 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | FROM PREVIOUS REVIEW: NUMBER FOR COMMENT | | | WILL REMAIN THE SAME AS FIRST REVIEW TO | | | AVOID CONFUSION. | | | | | | 3) SHT A5 SUBMIT CALCULATIONS FOR PRIM- | | | ARY AND SECONDARY ROOF DRAINS PER SECT- | | | IONS 1106 & 1107. SHOW SQUARE FOOTAGE OF | | | THE ROOF AND 1/2 AREA OF ALL VERTICAL | | | WALLS INCLUDING PARAPETS BEING ADDED TO | | | SF OF ROOF AREA. (THIS INCLUDES THE WALL | | | OF THE ADJACENT EXISTING BUILDING IF THE | | | BLDGS ARE ATTACHED). | | | 6) SUBMIT A WATER RISER DIAGRAM REQUIRED | | | BY SECTION 104.3.1.1. (NOTE: AIR CHAMB- | | | ERS ARE NOT APPROVED. WATER HAMMER ARR- | | | ESTORS REQUIRED BY SECTION 604.9 SHALL | | | BE LOCATED IN AN EFFECTIVE RANGE PER | | | PDI-WH 201 AND MANUF. INSTALLATION RE- | | | QUIREMENTS. | | | *********NEW COMMENT | | | 1B SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS553.80(2)(B). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|