| 2004-10-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04071120 |
| | ADD: 1308 CLARE AV |
| | CONT: BATTEN CONSTRUCTION |
| | TEL: (561)662-0309 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH LOCAL AMENDMENTS |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) LEGAL ISSUES: |
| | A) PROVIDE DEAD SHOWING OWNERSHIP |
| | B) PROVIDE DOCUMENTS FOR LOT SPLIT, SEE |
| | PLANNING. |
| | C) PROVIDE UNITY OF TITLE FOR LOTS |
| | 1,2&3. |
| | |
| | 3) FROM PREVIOUS REVIEW, COMMENT# 6 DELT |
| | WITH THE RATING OF THE EXTERIOR WALL |
| | 0-3' FROM THE PROPERTY LINE. FOR TYPE IV |
| | CONSTRUCTION THIS IS A 2 HR RATED BLOCK, |
| | SHEET A4 INDICATES THE USE OF UL BLOCK, |
| | PROVIDE THE EQUIVANT THICKNESS FOR BLOCK |
| | SUPPLIED BY UL. IF YOUR BLOCK IS TO BE |
| | SUPPLIED BY RINKER, THEN THE EQUIVALENT |
| | THICKNESS (TABLE 709.3.1) OF THE BLOCK |
| | WOULD BE SUPPLIED BY RINKER. |
| | |
| | 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXTERIOR LOUVERS. |
| | |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | IF THE PRODUCT APPROVALS SUBMITTED |
| | DO NOT HAVE "STATE APPROVAL" THEN LOCAL |
| | PRODUCT APPROVAL WILL BE REQUIRED. |
| | A) PROVIDE THE INDEPENDENT THIRD PARTY |
| | QUALITY ASSURANCE PRORGAM IF NOT DADE |
| | COUNTY NOA. |
| | B) FOR THE CERTIFIIED TESTING REPORT, |
| | THIS MUST BE A SEALED REPORT WITH |
| | THE 3RD PARTY QUALITY ASSURANCE |
| | ENTITY AND LOCAL PRODUCT APPROVAL |
| | COVER SHEET FILLED OUT. |
| | |
| | 6)FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 7)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. |
| | |
| | 8) THE WAREHOUSE REQUIRES 2 MEAN OF |
| | EGRESS, THE EGRESS THROUGH THE DOOR# 4 |
| | INTO THE RETAIL AREA CAN ONLY HAVE AN |
| | EXIT LIGHT ON THE WAREHOUSE SIDE. THE |
| | EXIT LIGHT ON THE RETAIL SIDE TO BE RE- |
| | MOVED. YOU CAN NOT TAKE A PERSON THROUGH |
| | A MORE DANGEROUS OCCUPANCY. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |