| 2004-08-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A4 MINIMUM FACILITIES REQUIRES A |
| | DRINKING FOUNTAIN. TABLE 403.1. ALSO SEE |
| | SECTION 410.1. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH 11-4.15 AND ALL SUBSECT- |
| | IONS. ALSO SEE SECTION 11-4..1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| | BENDING OR STOOPING. |
| | 2) SHT A4 CLEAR FLOOR SPACE IS REQUIRED |
| | FOR ALL ACCESSIBLE FIXTURES. 11-4.16.2 |
| | WATER CLOSETS, 11-4.19.3 LAVS, 11-4.22.3 |
| | TOILET ROOMS, & 11-4.24.5 SINKS SHALL |
| | SHOW CLEAR FLOOR SPACE TO ALLOW FORWARD |
| | APPROACH. |
| | 3) SHT A5 SUBMIT CALCULATIONS FOR PRIM- |
| | ARY AND SECONDARY ROOF DRAINS PER SECT- |
| | IONS 1106 & 1107. SHOW SQUARE FOOTAGE OF |
| | THE ROOF AND 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS BEING ADDED TO |
| | SF OF ROOF AREA. IF PRIMARY AND SECOND- |
| | ARY ROOF DRAINS ARE THRU THE SAME SCUPP- |
| | ER, THEN THE SCUPPER SHALL BE SIZED FOR |
| | THE TOTAL AREA REQUIRED FOR PRIMARY AND |
| | SECONDARY SCUPPER SIZE. |
| | 4) SHT A10 DETAIL #2/A10 SHOW COMPLIANCE |
| | WITH SECTION 11-4.19.4 EXPOSED PIPES AND |
| | SURFACES. |
| | 5) SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH 11-4.24 AND ALL SUBSECTIONS FOR THE |
| | BREAK ROOM SINK. |
| | 6) SUBMIT A WATER RISER DIAGRAM REQUIRED |
| | BY SECTION 104.3.1.1. (NOTE: AIR CHAMB- |
| | ERS ARE NOT APPROVED. WATER HAMMER ARR- |
| | ESTORS REQUIRED BY SECTION 604.9 SHALL |
| | BE LOCATED IN AN EFFECTIVE RANGE PER |
| | PDI-WH 201 AND MANUF. INSTALLATION RE- |
| | QUIREMENTS. |
| | |