Plan Review Notes
Plan Review Notes For Permit 04071120
Permit Number 04071120
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A4 MINIMUM FACILITIES REQUIRES A
 DRINKING FOUNTAIN. TABLE 403.1. ALSO SEE
 SECTION 410.1. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECT-
 IONS. ALSO SEE SECTION 11-4..1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 2) SHT A4 CLEAR FLOOR SPACE IS REQUIRED
 FOR ALL ACCESSIBLE FIXTURES. 11-4.16.2
 WATER CLOSETS, 11-4.19.3 LAVS, 11-4.22.3
 TOILET ROOMS, & 11-4.24.5 SINKS SHALL
 SHOW CLEAR FLOOR SPACE TO ALLOW FORWARD
 APPROACH.
 3) SHT A5 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106 & 1107. SHOW SQUARE FOOTAGE OF
 THE ROOF AND 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS BEING ADDED TO
 SF OF ROOF AREA. IF PRIMARY AND SECOND-
 ARY ROOF DRAINS ARE THRU THE SAME SCUPP-
 ER, THEN THE SCUPPER SHALL BE SIZED FOR
 THE TOTAL AREA REQUIRED FOR PRIMARY AND
 SECONDARY SCUPPER SIZE.
 4) SHT A10 DETAIL #2/A10 SHOW COMPLIANCE
 WITH SECTION 11-4.19.4 EXPOSED PIPES AND
 SURFACES.
 5) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH 11-4.24 AND ALL SUBSECTIONS FOR THE
 BREAK ROOM SINK.
 6) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. (NOTE: AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE LOCATED IN AN EFFECTIVE RANGE PER
 PDI-WH 201 AND MANUF. INSTALLATION RE-
 QUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]