Plan Review Notes
Plan Review Notes For Permit 04071102
Permit Number 04071102
Review Stop M
Sequence Number 1
Notes
Date Text
2004-08-12 00:00:00PROVISO:
 1.SUPPLY AND RETURN AIR NOT INDICATED
 IN OFFICE #105.
  
 2.PLAN SHEET ME1 INDICATES THE
 ADDITION OF 2 TRANSFER GRILLES.PLAN
 DOES NOT INDICATE IF THE EXISTING RETURN
 AIR IS A PLENUM OF A DUCTED RETURN.
 PLEASE NOTE, IF RETURN IS A PLENUM NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM.2001 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.