| Plan Review Notes For Permit 04071102 |
| Permit Number |
04071102 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-12 00:00:00 | PROVISO: | | | 1.SUPPLY AND RETURN AIR NOT INDICATED | | | IN OFFICE #105. | | | | | | 2.PLAN SHEET ME1 INDICATES THE | | | ADDITION OF 2 TRANSFER GRILLES.PLAN | | | DOES NOT INDICATE IF THE EXISTING RETURN | | | AIR IS A PLENUM OF A DUCTED RETURN. | | | PLEASE NOTE, IF RETURN IS A PLENUM NO | | | COMBUSTIBLES ALLOWED IN THE RETURN AIR | | | PLENUM.2001 FBC(M) 602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|