| Plan Review Notes For Permit 04071097 |
| Permit Number |
04071097 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-10 00:00:00 | 1) PLEASE EXPLAIN HOW THE PROPOSED | | | EQUIPMENT WILL RELATE TO EXITING. | | | PLEASE NOTE ON THE PLANS WHAT AREAS | | | WILL BE FREE EGRESS OR FAIL SAFE AREAS | | | AND WHAT IF ANY AREAS WILL BE FAIL | | | SECURE OR NO EGRESS. ALSO PLEASE | | | INDICATE ON THE PLANS HOW THIS EQUIPMENT | | | WILL RELATE TO THE MAKE-UP AIR | | | FEATURES OF THE SMOKE MANAGEMENT | | | SYSTEM FOR THE EGRESS DOORS. | | | PLEASE ALSO PROVIDE HOW FIRE ALARM | | | EQUIPMENT WILL BE INTERFACED WITH | | | ANY NEW SECURITY EQUIPMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|