| Plan Review Notes For Permit 04071089 |
| Permit Number |
04071089 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-06-14 00:00:00 | | | | | | | PROVISO | | | ```````````````````````````````````````` | | | ```````````````````````````````````````` | | | | | | RELOCATED PANEL "H" DOES NOT APPEAR TO | | | COMPLY WITH THE CLEARANCE REQUIREMENTS | | | OF 110.26. THIS COULD SIMPLY BE THE WAY | | | IT APPEARS ON THE DRAWING. IF IT IS IN | | | FACT IN VIOLATION THE PANEL OR DRYER | | | MUST BE MOVED. IF CORRECTED ACTION NEEDS | | | TO BE TAKEN, RESUBMIT SAME FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|