| Date |
Text |
| 2004-08-03 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1}PLEASE PROVIDE A CALCULATION |
| | INCLUDING ALL ADDED LOADS IMPOSED AND |
| | ALL EXISTING LOADS PER 215.15. |
| | |
| | 2} THE RANGE CALCULATION MUST COMPLY |
| | WITH 220.19, 2002 NEC. |
| | |
| | 3} THE SMALL APPLIANCE CALCULATION MUST |
| | COMPLY WITH 220.16 AND 210.11(C)(1), 20 |
| | AMP, #12 WIRE. |
| | |
| | 4} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BER ATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 5} INDICATE THE LOCATION OF THE SERVICE |
| | AND ALL RELATED EQUIPMENT ON DRAWINGS. |
| | |
| | 6} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 7} THE DINING ROOM RECEPTACLES MUST |
| | COMPLY WITH 210.52(B), 20 AMP. |
| | |
| | 8} SEE 220.3(B)(4) TO COMPUTE RECESSED |
| | LUMINAIRES. PLEASE ADD SAME TO LOAD |
| | CALCULATIONS, SHOW ON PLAN. |
| | |
| | 9} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS.FBC 905.2.2, NFPA-72 8-1.4. |
| | |
| | 10} PLEASE LIST THE REQUIREDD ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |