 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED AND
 ALL EXISTING LOADS PER 215.15.
  
 2} THE RANGE CALCULATION MUST COMPLY
 WITH 220.19, 2002 NEC.
  
 3} THE SMALL APPLIANCE CALCULATION MUST
 COMPLY WITH 220.16 AND 210.11(C)(1), 20
 AMP, #12 WIRE.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BER ATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 5} INDICATE THE LOCATION OF THE SERVICE
 AND ALL RELATED EQUIPMENT ON DRAWINGS.
  
 6} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 7} THE DINING ROOM RECEPTACLES MUST
 COMPLY WITH 210.52(B), 20 AMP.
  
 8} SEE 220.3(B)(4) TO COMPUTE RECESSED
 LUMINAIRES. PLEASE ADD SAME TO LOAD
 CALCULATIONS, SHOW ON PLAN.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.FBC 905.2.2, NFPA-72 8-1.4.
  
 10} PLEASE LIST THE REQUIREDD ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026