| Plan Review Notes For Permit 04071021 |
| Permit Number |
04071021 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-26 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SUBMIT CONDUIT & WIRE SIZE FOR ALL | | | NEW WIRING BEING INSTALLED OR EXISTING | | | WIRING BEING REUSED. | | | | | | 2} INDICATE THE NAMEPLATE RATING OF THE | | | UNIT(S) BEING INSTALLED.IF ADDED UNITS | | | OR LARGER REPLACEMENT UNITS, PROVIDE | | | LOAD CALCS. | | | | | | 3} INDICATE CIRCUIT NUMBERS BEING USED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|