| Plan Review Notes For Permit 04070992 |
| Permit Number |
04070992 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-30 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)SEPARATE PERMITS REQUIRED. | | | | | | 3.)A CERTIFICATE OF AUTHORIZATION IS | | | REQUIRED FOR ANDREW MORGAN SERVICES PER | | | CARRIE FLYNN OF FPBE.MR. MORGAN HAS | | | BEED ADVISED OF THIS IN WRITING FROM | | | THIS OFFICE TWICE.SEE ATTACHED. | | | FAC61G15-23.002, FS471.025. | | | | | | 4.)SPECIFY THE SLOPE FOR THE "NEW | | | ACCESSIBLE RAMP", C1, BOTTOM LEFT. | | | | | | 5.)SUBMIT PRODUCT APPROVALS FOR THE | | | MODIFIED ROOF FOR REVIEW, OR CAN BE | | | SUBMITTED WITH THE ROOF PERMIT | | | APPLICATION. | | | | | | 6.)STUCCO IN A VERTICAL APPLICATION | | | IS REQUIRED TO BE 7/8" MIN. (7-A2), | | | FBC2504.2.2, ASTMC926.CHECK ALL | | | DETAILS. | | | | | | 7.)DECLARE A BUILDING TYPE.IS THIS | | | BUILDING SPRINKLED? IF IT IS, SPRINKLERS | | | ARE REQUIRED (NOTE REQUIREMENT, IF ANY, | | | ON PLAN).IF REQUIRED, SUBMIT SPRINKLER | | | PLANS FBC104.3.1.1(5). |
|