| Plan Review Notes For Permit 04070961 |
| Permit Number |
04070961 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} HAND DRAWN REVISIONS MUST BE | | | INITIALED BY THE DESIGNER OF RECORD. | | | PASTED ON NOTES AND SCHEDULES ARE NOT | | | ACCEPTABLE. | | | | | | 2} THE SEAL OF THE DESIGNER MUST | | | CONTAINTHE DATE SEALED PER 61G1-16.003 | | | FAC. | | | | | | 3} THE TITLE BLOCK MUST CONTAIN ALL | | | INFORMATION REQUIRED BY 61G1-16.004 FAC. | | | INCLUDING FIRM #, TELEPHONE NUMBER AND | | | ADDRESS. SEE FS 481 AND RELEVANT | | | ADMINISTRATIVE CODES. | | | | | | 4} PLEASE RECALCULATE THE LOAD AND | | | CHANGE PANEL SCHEDULE TO REFLECT THE | | | ADDED RECESSED LUMINAIRES PER | | | 220.3(B)(4) NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|