| 2006-09-22 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} 250.52(A)(3) CONCRETE-ENCASED |
| | ELECTRODE. |
| | AN ELECTRODE ENCASED BY AT LEAST 50 MM |
| | (2 IN.) OF CONCRETE, LOCATED WITHIN AND |
| | NEAR THE BOTTOM OF A CONCRETE FOUNDATION |
| | OR FOOTING THAT IS IN DIRECT CONTACT |
| | WITH THE EARTH, ETC.IF THE SERVICE IS |
| | NEW THIS REQUIREMENT SHOULD HAVE BEEN |
| | ADDRESED WHEN FOOTER STEEL WAS |
| | INSTALLED. ISSUES LIKE THIS IS WHY WE |
| | REQUIRE THE PROPOSED WORK BE COMPLETE |
| | AND CORRECT ON THE PLANS SUBMITTED FOR |
| | REVIEW. |
| | |
| | 2} THE EQUIPMENT GROUNDING CONDUCTOR |
| | MUST COMPLY WITH 250.66. THE NOTE ON THE |
| | COMMENT SHEET STATINDG THAT THE #4 IS |
| | "OVERSIZED" IS INCORRECT. THE LARGEST |
| | SERVICE ENTRANCE CONDUCTOR AS STATED IN |
| | 250.66 IS PARALLEL 2/0. SEE EXHIBIT |
| | 250.28 IN THE HANDBOOK FOR |
| | CLARIFICATION. THE DESIGNER INDICATES A |
| | 400 AMP SERVICE IS BEING SUPPLIED. 400 |
| | MCM WOULD BE A 1/0 GEC. IF THE EXAMPLE |
| | IN THE HANDBOOK IS USED, THE GEC WOULD |
| | BE #2CU,(133100CMX2, ROUNDED UP) THEN |
| | TECHNICALLY THE SERVICE IS ONLY RATED |
| | FOR 350 AMPS. |
| | |
| | 3} THE CONDUCTOR SIZES WERE REMOVED FROM |
| | THE SCHEDULE, PLEASE PUT THEM BACK ON |
| | SOTHAT OCP AND CONDUCTOR SIZE CAN BE |
| | REVIEWED FOR COMPLIANCE PER 310.16. |
| | |
| | 4} CIRCUIT #B5 IS MARKED AS A SMALL |
| | APPLIANCE CIRCUIT IN THE SCHEDULE, BUT |
| | IS THE BATH CIRCUIT ON TEH PLAN. |
| | |
| | 5} AHU #1 IS NOT LISTED ON THE SCHEDULE. |
| | |
| | 6} A/C COMPRESSER #1 IS NOT LISTED AND |
| | HAS THE WRONG CIRCUIT NUMBERS AT THE |
| | UNIT ON THE PLAN. |
| | |
| | 7} PER 210.12 CIRCUIT G5 (SMOKE |
| | DETECTORS) MUST BE ON A AFCI. THEY |
| | CANNOT BE ON THE BATHROOM CIRCUIT, SEE |
| | 210.11(C)(3). |
| | |
| | 8} THE INITIALS ON THE ARCHITECTS SEAL |
| | IS NOT THE SAME AS THE "SIGNATURE" ON |
| | THE SEAL DATED 8/13/04. THE ARCHITECT |
| | MUST SIGN HIS SEAL PER 61G1-16.003 |
| | FLORIDA ADMINISTRATIVE CODE. ONE SET OF |
| | PLANS IS BEING RETAINED BY THIS OFFICE |
| | WITH THIS APPARANTLY UNAUTHORIZED " |
| | SIGNATURE". |
| | |
| | |