Text |
| 2006-07-10 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE REVISED PLAN SHOWS AN EXISTING |
| | SERVICE THAT DOES NOT CORRELATE WITH THE |
| | "EXISTING SERVICE" SUBMITTED ON THE |
| | ORIGINAL PLAN. THIS WILL BE REVIEWED AS |
| | A NEW SERVICE, AND THE FOLLOWING |
| | COMMENTS APPLY. |
| | A)PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | B) THE GROUNDING ELECTRODE MUST COMPLY |
| | WITH THE MINIMUM SIZE FOR THE SERVICE |
| | PER 250.66. |
| | C) THE RISER INDICATES THE MAINS IN THE |
| | PANELS, THE PLAN SHOWS A MAIN DISCONNECT |
| | AT THE METER. PLEASE INDICATE PROPOSED |
| | INTENTION. |
| | D) ALL AVAILABLE ELECTRODES MUST BE |
| | BONDED PER 250.50. |
| | |
| | 2} INDICATE THE LOCATION OF THE PANELS |
| | ON THE PLAN. |
| | |
| | 3} THE RISER SHOWS PANEL "A" FEEDING |
| | PANEL "G", BUT NOT SHOWN ON THE PANEL |
| | SCHEDULE.INDICATE FEEDER AND OCP SIZE IN |
| | THE SCHEDULE. |
| | |
| | 4} THE CIRCUIT NUMBERS DESIGNATIONS ARE |
| | DUPLICATED IN BOTH PANELS. PLEASE USE |
| | PANEL DESIGNATION (1A)FOR CIRCUIT #1 |
| | PANEL "A". |
| | |
| | 5} CIRCUIT 17B AND 19A HAS AN INCORRECT |
| | OCP (25 AMPS), AND WIRE SIZE(#10) FOR |
| | THE 10300 WATT LOAD. 310.16. |
| | |
| | 6} CIRCUITS 1 AND 3, PANEL "G", SAME |
| | COMMENT AS #5. |
| | |
| | 7} THE WIRE SIZE IS TOO SMALL SMALL FOR |
| | THE LOAD AND OCP, CIRCUIT 2 &4, PANEL |
| | "G". 310.16. |
| | |
| | 8} CIRCUIT #2A, PANEL"A", BATH#2 MUST |
| | COMPLY WITH 210.11(C)(3), IF SERVING THE |
| | RECEPTACLE. |
| | |
| | 9) THE ELECTRICAL NOTES INDICATE A |
| | MINIMUM WIRE SIZE OF #12, BUT #14 IS |
| | SHOWN ON THE PANEL SCHEDULE IN SEVERAL |
| | PLACES. PLEASE ADJUST THE NOTE OR CHANGE |
| | THE SCHEDULE TO REFLECT THE NOTE. THIS |
| | IS THE SECOND TIME THIS COMMENT HAS BEEN |
| | MADE. |
| | |
| | 10} NOTE 24 IS CODE COMPLIANT AS LONG AS |
| | THE CIRCUIT IS AFCI PROTECTED PER |
| | 210.12. |
| | |
| | 11} SMOKE DETECTORS ARE REQUIRED PER |
| | 313.1 FBC. |
| | |
| | 12} RECEPTACLES ARE REQUIRED WITHIN 25' |
| | OF THE CONDENSING UNITS PER 210.63. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |