| Plan Review Notes For Permit 04070897 |
| Permit Number |
04070897 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-03-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT P7 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. | | | A) BATHTUB TRAP IS AN "S" TRAP WHICH IS | | | NOT APPROVED. SECTION 1002.3(5) | | | B) EVERY DRY VENT CONNECTING TO A | | | HORIZONTAL DRAIN PIPE SHALL CONNECT | | | ABOVE THE CENTERLINE OF THE HORIZONTAL | | | DRAIN PIPE. SECTION 905.3. (SEE VENT | | | UPSTREAM OF THE W/C). | | | C) PIPE SIZING IS NOT CORRECT. MINIMUM | | | 3" REQUIRED TO THE W/C, AND MINIMUM 2" | | | UNDERGROUND TO THE TUB. TABLE 709.1 | | | FOOTNOTE D, AND SECTION 710.3. | | | 2) SEE REDLINE EXAMPLE OF A SANITARY | | | RISER DIAGRAM THAT MEETS CODE | | | REQUIREMENTS THAT WAS SENT BACK WITH THE | | | LAST COMMENTS. IF INSTALLED AS SHOWN ON | | | RISER DIAGRAM SUBMITTED, THE | | | INSTALLATION WILL NOT PASS INSPECTION IN | | | THE FIELD. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|