| Plan Review Notes For Permit 04070897 |
| Permit Number |
04070897 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-03-31 00:00:00 | *** DENIED *** | | | 1) PLEASE SUBMIT A COMPLETE MANUAL 'J' | | | CALCULATION SHOWING CFM'S AND DUCT SIZES | | | TO EACH ROOM, PER 20044 FBC/R M1401.3 . | | | | | | 2) DUCT SIZES APPEAR NON-FUNCTIONAL, | | | PLEASE RESIZE DUCTS ACCORDING TO THE | | | MANUAL 'J' CALCULATIONS. | | | | | | 3) PLEASE SHOW JOB ADDRESS ON MECHANICAL | | | PLANS. | | | | | | 4)ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|