Plan Review Notes
Plan Review Notes For Permit 04070897
Permit Number 04070897
Review Stop M
Sequence Number 4
Notes
Date Text
2006-03-31 00:00:00*** DENIED ***
 1) PLEASE SUBMIT A COMPLETE MANUAL 'J'
 CALCULATION SHOWING CFM'S AND DUCT SIZES
 TO EACH ROOM, PER 20044 FBC/R M1401.3 .
  
 2) DUCT SIZES APPEAR NON-FUNCTIONAL,
 PLEASE RESIZE DUCTS ACCORDING TO THE
 MANUAL 'J' CALCULATIONS.
  
 3) PLEASE SHOW JOB ADDRESS ON MECHANICAL
 PLANS.
  
 4)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.