| Plan Review Notes For Permit 04070897 |
| Permit Number |
04070897 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-02-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT P7 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. | | | A) EVERY DRY VENT CONNECTING TO A | | | HORIZONTAL DRAIN PIPE SHALL CONNECT | | | ABOVE THE CENTERLINE OF THE HORIZONTAL | | | DRAIN PIPE. SECTION 905.3. (SEE VENTS | | | FOR THE W/C AND TUB). | | | B) SANITARY CROSS FITTINGS ARE NOT | | | APPROVED. FITTINGS SHALL BE INSTALLED TO | | | GUIDE SEWAGE AND WASTE IN THE DIRECTION | | | OF FLOW. SECTION 706.3. (SEE CONNECTIONS | | | TO W/C AND TUB). | | | C) TRAP AT W/C NOT APPROVED. W/C HAS AN | | | INTREGRAL TRAP IN FIXTURE. SECTION | | | 1002.1. | | | 2) SEE REDLINE EXAMPLE OF A SANITARY | | | RISER DIAGRAM THAT MEETS CODE | | | REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|