Plan Review Notes
Plan Review Notes For Permit 04070897
Permit Number 04070897
Review Stop P
Sequence Number 3
Notes
Date Text
2005-02-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P7 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN PIPE SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAIN PIPE. SECTION 905.3. (SEE VENTS
 FOR THE W/C AND TUB).
 B) SANITARY CROSS FITTINGS ARE NOT
 APPROVED. FITTINGS SHALL BE INSTALLED TO
 GUIDE SEWAGE AND WASTE IN THE DIRECTION
 OF FLOW. SECTION 706.3. (SEE CONNECTIONS
 TO W/C AND TUB).
 C) TRAP AT W/C NOT APPROVED. W/C HAS AN
 INTREGRAL TRAP IN FIXTURE. SECTION
 1002.1.
 2) SEE REDLINE EXAMPLE OF A SANITARY
 RISER DIAGRAM THAT MEETS CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]