| Date |
Text |
| 2005-02-14 00:00:00 | DENIED |
| | |
| | NOTES NOT ADDRESSED FROM LAST REVIEW. |
| | |
| | 5.A MINIMUM 8" CLEARANCE BETWEEN FLOOR |
| | JOISTS AND GROUND IS REQUIRED OR PT |
| | LUMBER CAN BE USED.SHOW ON PLANS |
| | FBC 2304.3.3 |
| | |
| | 10.ALL PRODUCT APPROVALS QUITH QUALITY |
| | ASSURANCE (MIAMI-DADE) FOR EXAMPLE |
| | REQUIRE THE FOLLOWING. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | NO QUALITY ASSURANCE REPORTS WERE |
| | SUBMITTED ITH STATE APPROVALS. |
| | |
| | NEW COMMENT:PLANS ARE REQUIRED TO HAVE |
| | ORIGONAL PRINTED NAME AND SIGNATURE OF |
| | THE PERSON RESPOSIBLE FOR THE DESIGN. |
| | FBC 104.2.1 |
| | |
| | ANY QUESTIONS CALL ME. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |