Plan Review Notes
Plan Review Notes For Permit 04070897
Permit Number 04070897
Review Stop M
Sequence Number 1
Notes
Date Text
2004-08-02 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW.
 PLEASE PROVIDE THE FOLLOWING:
 1.A COMPLETED FORM 600C PER THE 2001
 FBC CHAPTER 13 SUB-CHAPTER 6 METHOD C.
  
 2.PROVIDE EQUIPMENT SCHEDULE. INDICATE
 IF THE EQUIPMENT IS NEW OR EXISTING.
  
 3.PROVIDE DUCT & GRILLE SIZE, MATERIAL
 AND LAYOUT.
  
 4.INDICATE LOCATION OF THE AIR HANDLER
 AS WELL AS THE CONDENSING UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.