| Plan Review Notes For Permit 04070897 |
| Permit Number |
04070897 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE NOTE ON SHEET P-1 INCORRECTLY | | | REFERS TO 2003 FBC.WE ARE CURRENTLY | | | UNDER2001, AND 2002 NEC. | | | | | | 2} THE 15 AMP BREAKER FOR THE BATH | | | CIRCUIT ON SHEET 9-12 MUST BE 20 AMP | | | WITH #12CU WIRE TO COMPLY WITH | | | 210.11(C)(3). | | | | | | 3} SMOKE DETECTORS ARE REQUIRED PER NFPA | | | -72 ART. 8-1.4, INSIDE AND OUTSIDE | | | BEDROOMS. | | | | | | 4} RECEPTACLES MUST BE ADDED IN THE | | | LIBRARY TO COMPLY WITH SPACING PER | | | 210.52(A). | | | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPON-SIBLE FOR THE DESIGN. SECTION | | | 104.2.1 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|