Plan Review Notes
Plan Review Notes For Permit 04070897
Permit Number 04070897
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE NOTE ON SHEET P-1 INCORRECTLY
 REFERS TO 2003 FBC.WE ARE CURRENTLY
 UNDER2001, AND 2002 NEC.
  
 2} THE 15 AMP BREAKER FOR THE BATH
 CIRCUIT ON SHEET 9-12 MUST BE 20 AMP
 WITH #12CU WIRE TO COMPLY WITH
 210.11(C)(3).
  
 3} SMOKE DETECTORS ARE REQUIRED PER NFPA
 -72 ART. 8-1.4, INSIDE AND OUTSIDE
 BEDROOMS.
  
 4} RECEPTACLES MUST BE ADDED IN THE
 LIBRARY TO COMPLY WITH SPACING PER
 210.52(A).
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPON-SIBLE FOR THE DESIGN. SECTION
 104.2.1
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved