| Plan Review Notes For Permit 04070881 |
| Permit Number |
04070881 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-22 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE #6 GROUND BETWEEN THE DISCONNECTS | | | IS IN VIOLATION OF 250.6. | | | | | | 2} PLEASE LIST ALL THE REQUIRED | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.11C3 | | | | | | 3} THE STEAM SHOWER IS NOT IN THE LOAD | | | CALCULATION. | | | | | | 4} PLEASE PROVIDE PANEL SCHEDULES FOR | | | ALL PANELS SO THAT COMPLIANCE OF BRANCH | | | CIRCUITS CAN BE DETERMINED. | | | | | | 5} THE DISCONNECTS BEHIND THE CONDENSING | | | UNITS DO NOT COMPLY WITH CLEARANCE | | | REQUIREMENTS OF 110.26. | | | | | | 6} SMOKE DETECTORS ARE REQUIRED PER 8-1. | | | 4.1.6.2 NFPA-72, AND 905.2 FBC.. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|