Plan Review Notes
Plan Review Notes For Permit 04070865
Permit Number 04070865
Review Stop E
Sequence Number 3
Notes
Date Text
2005-04-27 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS MUST CONTAIN
 ORIGINAL SIGNATURE WHEN SIGNING AND
 SEALING PLANS.
 FS 481.221
 PLEASE SEE PLANS SUBMITTED ARE SEALED
 PHOTOCOPIES OF SIGNED PLANS.
  
 2)NOTE: PLEASE SEE RISER HAS NOW
 COMPLETELY CHANGED FROM ORIGINAL PLANS.
 PLEASE SEE THERE IS NO MAIN SHOWN? ETC.
 PLEASE SEE 215.5,240.4,225.31-36,230.70
 240.4 ETC.
  
 3)NOTE: PLEASE SEE PANEL IS SHOWN AS MLO
 WITH OUT ANY MAIN.225.31 ETC.
  
 4)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN FROM METER
 TO MAIN?
 PLEASE SEE 250.6,250.24.
  
 5)NOTE: PLEASE SEE THE # OF CONDUCTORS
 SHOWN FROM MAIN PANEL TO SUB PANEL.
 2-HOTS, AND ONE GROUND AS NOTED.???
 215.5
  
 6)NOTE: PLEASE SEE "WHITE OUT" AND
 HANDDRAWN CHANGES ON PLANS WHICH ARE NOT
 PERMITTED TO SIGNED AND SEALED PLANS.
 FS 481.221
  
 7)NOTE: PLEASE SEE ONE COPY OF PLANS
 SUBMITTED ARE NOW BEING RETAINED FOR
 POSSIBLE REVIEW BY THE DBPR AND STATE
 BOARD FOR ARCHITECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  