Plan Review Notes
Plan Review Notes For Permit 04070865
Permit Number 04070865
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-22 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN
 ON PANEL SCHEDULE BUT NO GFI SHOWN ON
 PLANS.
  
 2)NOTE: PLEASE SEE DEDICATED CIRCUIT
 SHOWN FOR GOLF CHARGER BUT NOT ON PANEL
 SCHEDULE.
  
 3)NOTE: PLEASE SEE 210.52D FOR MISSING
 GFI TO BE W/IN 3' FROM LAV.
  
 4)NOTE: PLEASE SEE 210.52 FOR A COUPLE
 OF MISSING RECEPTS.
  
 5)NOTE: PLEASE SEE 210.52C3,5 FOR PENIN-
 -SULAR SPACE.
  
 6)NOTE: PLEASE SEE OCP SHOWN FOR AHU #2,
 5.5KW W/ 50 OCP.
 424.3B
  
 7)NOTE: PLEASE SEE 250.122 FOR SIZING
 OF EQUIPMENT GROUNDING CONDUCTORS.
 #4 SHOWN FOR BOTH SUB PANELS, WHICH IS
 PERMITTED BUT OVERSIZED. THIS IS ONLY
 A NOTE. IF SHOWN THIS SIZE ON PLAN,
 THEN THEY WILL BE REQUIRED TO BE PUT IN.
  
 PLEASE PROVIDE RM DESIGNATION ON PLANS.
 PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW