| Plan Review Notes For Permit 04070865 |
| Permit Number |
04070865 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-22 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN | | | ON PANEL SCHEDULE BUT NO GFI SHOWN ON | | | PLANS. | | | | | | 2)NOTE: PLEASE SEE DEDICATED CIRCUIT | | | SHOWN FOR GOLF CHARGER BUT NOT ON PANEL | | | SCHEDULE. | | | | | | 3)NOTE: PLEASE SEE 210.52D FOR MISSING | | | GFI TO BE W/IN 3' FROM LAV. | | | | | | 4)NOTE: PLEASE SEE 210.52 FOR A COUPLE | | | OF MISSING RECEPTS. | | | | | | 5)NOTE: PLEASE SEE 210.52C3,5 FOR PENIN- | | | -SULAR SPACE. | | | | | | 6)NOTE: PLEASE SEE OCP SHOWN FOR AHU #2, | | | 5.5KW W/ 50 OCP. | | | 424.3B | | | | | | 7)NOTE: PLEASE SEE 250.122 FOR SIZING | | | OF EQUIPMENT GROUNDING CONDUCTORS. | | | #4 SHOWN FOR BOTH SUB PANELS, WHICH IS | | | PERMITTED BUT OVERSIZED. THIS IS ONLY | | | A NOTE. IF SHOWN THIS SIZE ON PLAN, | | | THEN THEY WILL BE REQUIRED TO BE PUT IN. | | | | | | PLEASE PROVIDE RM DESIGNATION ON PLANS. | | | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|