| Date |
Text |
| 2004-07-22 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002. |
| | TITLE BLOCK REQUIRED TO HAVE ALL PRINTED |
| | INFORMATION AS SETFORTH PER ABOVE REF. |
| | LIC #? |
| | |
| | 2)NOTE: PLEASE SEE 424.3B FOR OCP FOR |
| | AHU HEAT. MIN 125% |
| | |
| | 3)NOTE: PLEASE SEE NOTE FOR SD'S TO BE |
| | WIRED TO KITCH/BATH LT CIRCUITS. |
| | PLEASE SEE THE FOLLOWING NOTE: 210.12 |
| | |
| | 4)NOTE: PLEASE SEE NOTE ON PLANS MENTION |
| | 'S ALL RECEPTS TO BE AFCI. PLEASE SEE |
| | WE ARE UNDER THE 2002 NEC. PLEASE SEE |
| | 210.12, REQUIRED TO PROTECT ALL"OUTLETS" |
| | INCL. SD'S, LTS, RECEPTS, FANS ,,,, |
| | IF SD'S ARE WIRED TO KIT OR BATH CIRCUIT |
| | 'S, THE AFCI PROETCTION WILL BE REQUIRED |
| | FOR THOSE CIRCUITS ALSO. |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | MISSING ALL SD'S REQUIRED. |
| | |
| | 6 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 7)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS ON WALL SPACE. |
| | |
| | 8) NOTE: PLEASE SEE 210.52D FOR MISSING |
| | GFI RECEPTS REQUIRED W/IN 3'OF LAV. |
| | |
| | 9)NOTE: PLEASE SEE SPACING ON KITCHEN |
| | COUNTER RECEPTS. 210.52C1 |
| | |
| | 10)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| | BE A RECEPT SHOWN IN THE MIDDLE OF |
| | BAR SINK? GFI? 210.8 |
| | |
| | 11)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | PLEASE PROVIDE RM DESIGNATIONS ON PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLYINSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |