2005-11-21 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SEE NO ELECTRICAL
 REVISION SUBMITTED INCLUDING GENERATOR
 MAY BE DONE UNTIL PERMIT IS ISSUED FOR
 GENERATOR. PLEASE SEE PLANS ARE NOW
 INLCUDING GEN, WHEN ORIGINAL PLANS
 CALLED FOR THIS BEING FUTURE.
  
 2)NOTE: PLEASE ALSO CORRELATE SIZING OF
 GEN WITH GEN PERMIT APPLICATION.
  
 3)NOTE: PLEASE PROVIDE LOAD CALCS FOR
 GEN PANEL TO INCLUDE LOADS FOR HEAT AT
 100% OR PLEASE PROVIDE A DETAIL FOR ANY
 LOAD SHEDDING WHICH MAY TAKE PLACE.
 702.5, 240.4 ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ONCE GEN PERMIT IS ISSUED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  