| Plan Review Notes For Permit 04070860 |
| Permit Number |
04070860 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-11-21 00:00:00 | **** UNSAT **** | | | | | | | | | 1)NOTE: PLEASE SEE NO ELECTRICAL | | | REVISION SUBMITTED INCLUDING GENERATOR | | | MAY BE DONE UNTIL PERMIT IS ISSUED FOR | | | GENERATOR. PLEASE SEE PLANS ARE NOW | | | INLCUDING GEN, WHEN ORIGINAL PLANS | | | CALLED FOR THIS BEING FUTURE. | | | | | | 2)NOTE: PLEASE ALSO CORRELATE SIZING OF | | | GEN WITH GEN PERMIT APPLICATION. | | | | | | 3)NOTE: PLEASE PROVIDE LOAD CALCS FOR | | | GEN PANEL TO INCLUDE LOADS FOR HEAT AT | | | 100% OR PLEASE PROVIDE A DETAIL FOR ANY | | | LOAD SHEDDING WHICH MAY TAKE PLACE. | | | 702.5, 240.4 ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW ONCE GEN PERMIT IS ISSUED. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|