Plan Review Notes
Plan Review Notes For Permit 04070860
Permit Number 04070860
Review Stop P
Sequence Number 3
Notes
Date Text
2004-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 PLUMBING
  
 1) SHT A8 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) MASTER BATH CROSS FITTING NOT APPRO-
 VED AT WATER CLOSET. SECTION 706.1
 B) SINK SHALL DISCHARGE DOWNSTREAM OF
 THE HORIZONTAL DRY VENT FOR THE POWDER
 ROOM. SECTION 909.1
 C) WASH MACHINE AND LAUNDRY SINK SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT FOR BATH #3. SECTION 909.1
 D) WASH MACHINE SHALL CONNECT TO THE
 STACK BELOW THE TUB AT THE SECOND FLOOR.
 SECTION 901.2
 2) SEE ATTACHED SHEETS SHOWING EXAMPLE
 OF RISER DIAGRAM SECTIONS THAT MEET CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]