| Plan Review Notes For Permit 04070860 |
| Permit Number |
04070860 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-07 00:00:00 | -----------------DENIED----------------- | | | 1.SHOW AREAS BEING SERVED BY MINI-SPLIT | | | A/C SYSTEMS, SHOW EQUIP. ON SCHEDULE | | | 2.MASTER BATH: EF REQUIRED AT EACH WATER | | | CLOSET AND SHOWER/BATH AREA | | | 3.AHU'S IN ATTIC TO BE MIN 6' FROM ATTIC | | | ACCESS PER FBC CH 13 SEC | | | 610.1.ABC.3.5.2 | | | 4.DRYER EXHAUST AND WATER HEATER VENTS | | | REQUIRED (NOT SHOWN ON PLAN). | | | 5.COMBUSTION AIR REQUIRED IN LAUNDRY | | | IF DRYER IS GAS (NOT INDICATED ON | | | PLAN). | | | 6.BEDROOM #2 SUPPLY DUCT SIZE NOT SHOWN. | | | | | | ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561-805-6734 |
|