2004-08-07 00:00:00-----------------DENIED-----------------
 1.SHOW AREAS BEING SERVED BY MINI-SPLIT
 A/C SYSTEMS, SHOW EQUIP. ON SCHEDULE
 2.MASTER BATH: EF REQUIRED AT EACH WATER
 CLOSET AND SHOWER/BATH AREA
 3.AHU'S IN ATTIC TO BE MIN 6' FROM ATTIC
 ACCESS PER FBC CH 13 SEC
 610.1.ABC.3.5.2
 4.DRYER EXHAUST AND WATER HEATER VENTS
 REQUIRED (NOT SHOWN ON PLAN).
 5.COMBUSTION AIR REQUIRED IN LAUNDRY
 IF DRYER IS GAS (NOT INDICATED ON
 PLAN).
 6.BEDROOM #2 SUPPLY DUCT SIZE NOT SHOWN.
  