| Date |
Text |
| 2004-07-22 00:00:00 | ************ UNSAT ******************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G1-16.004, |
| | PLEASE INCLUDE ALL LICENSE #'S AND |
| | PRINTED NAMES AS REQUIRED PER ABOVE. |
| | PLEASE SEE FS 481.219 FOR REQUIRED LICEN |
| | -SE # MISSING. |
| | PLEASE ALSO SEE FS 481.221, MUST CONTAIN |
| | SIGNATURE. PLEASE SEE THAT PLANS APPEAR |
| | TO BE INITIALED AT THIS TIME. IF THIS |
| | IS ACTUAL "LEGAL" SIGNATURE, PLEASE |
| | PROVIDE A SIGNED,SEALED AND NOTARIZED |
| | LETTER STATING IT IS YOUR LEGAL SIG. |
| | WE WILL PLACE IN OUR SIGNATURE FILE FOR |
| | FUTURE REFERENCE . |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: PLEASE LABEL PANELS AND LABEL |
| | PANELS ON PLANS. MULTIPLE PANELS ARE |
| | SHOWN AS BEING LEFTSIDE AND OR RIGHTSIDE |
| | |
| | 4)NOTE: PLEASE SEE RISER INDICATE A |
| | PANEL FOR GEN PANEL, YET THERE IS NO |
| | PANEL SCHEDULE FOR THIS. PLEASE ALSO |
| | IDENTIFY ON PLANS. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE SHOW GROUNDING ELETRODE |
| | SYSTEM PER 250.50. FOOTER STEEL/COLD |
| | WATER/ ETC. |
| | |
| | 6) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 7)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | SOME ARE REDLINED ON PLANS. |
| | |
| | 8) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | SOME AREA REDLINED ON PLANS. |
| | |
| | 9 )NOTE: PLEASE SHOW /CLARIFY METHOD |
| | OF THE EQUIPMENT GROUNDING BETWEEN |
| | MAIN MEANS OOF DISC AND PANELS/GUTTERS. |
| | 250.110,250.24 |
| | PLEASE SIZE ALL EQUIPMENT GROUNDING |
| | CONDUCTORS PER 250.122 |
| | |
| | 10)NOTE: PLEASE INDICATE ALL A/C UNITS |
| | ON PLANS AND DISCONNECTS PER 440.11 |
| | |
| | 11)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 12)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | RECESSED FIX MAY ONLY BE FIGURED IN |
| | GENERAL LT IF LTS ARE MIN FOR EGRESS/ |
| | GEN LT. |
| | |
| | 13)NOTE: PLEASE CORRELATE AND LABEL |
| | A/C UNTIS ON PANEL SCHEDULE(S). |
| | PLEASE SEE A COUPLE SHOWN AS SAME ?? |
| | |
| | 14)NOTE: PLEASE SEE 424.3B FOR MIN OVER- |
| | -CURRENT PROTECTION TO BE 125%. |
| | |
| | 15)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN |
| | ON PANEL SCHEDULE BUT GFI RECEPT NOT |
| | LOCATED OR INDICATED ON PLANS?680 |
| | IS THIS MASTER BATH? |
| | |
| | 16)NOTE: PLEASE SEE SOME A/C UNITS LOADS |
| | ARE SHOWN AS 20A'S AND OCP IS 20A'S, |
| | PLEASE SEE LOADING OF BRKR AT 80%? |
| | PLEASE ALSO VERIFY AHU #4 SHOWN AS 2P20A |
| | IS THERE NO HEAT FOR THIS UNIT? |
| | PLEASE CORRELATE TOTAL A/C KW IN LOAD |
| | CALCULATIONS AND WHAT IS INDICATED ON |
| | PANELS. |
| | 215.5 |
| | PLEASE SEE LOAD SHOWN FOR 15KW UNIT? |
| | PLEASE VERIFY THIS? |
| | |
| | 17)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | -S ON PLANS. |
| | |
| | 18)NOTE: PLEASE SEE PLANS INDICATED 3 |
| | GDO'S ON RIGHT-SIDE HOWEVER ONLY TWO |
| | ARE INDICATED ON PANEL SCHEDULE? PLEASE |
| | VERIFY IF THESE ARE SHARED. |
| | |
| | 19)NOTE: PLEASE ALSO SEE THERE APPEARS |
| | TO BE DEDICATED GOLF CART CHARGER RECEPT |
| | -S ON GARAGE WALLS, YET THESE ARE NOT |
| | INDICATED ON PANEL SCHEDULES? |
| | PLEASE VERIFY. 215.5 |
| | |
| | 20)NOTE: PLEASE SEE 210.52H FOR RECEPTS |
| | REQUIRED IN HALLS/HALL AREAS 10' OR MORE |
| | |
| | 21)NOTE: PLEASE VERIFY WASH/DRYER SHOWN |
| | ON SECOND FLOOR APPEARS TO BE A SINGLE |
| | STACKABLE UNIT? PANEL SCHEDULE INDICATE |
| | UNITS AS BEING SEPARATE? |
| | |
| | 22)NOTE: PLEASE SEE 210.52C1, APPEARS TO |
| | HAVE ONE RECEPT MISSING FOR KITCHEN |
| | COUNTERSPACE. |
| | |
| | 23)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND STAMP- |
| | -ING. ONE SET OF OLD MAY BE SUBMITTED |
| | FOR REFERENCE ONLY. |
| | |
| | 24)NOTE: PLEASE SEE THERE IS NO SYMBOL |
| | SCHEDULE/LIST SHOWN. |
| | |
| | *** NOTE*** |
| | PLEASE SEE NO OTHER LV IS SHOWN ON PLANS |
| | ONLY CATV AND PHONE AT THIS TIME. |
| | PLEASE KNOW IF THERE IS GOING TO BE ANY |
| | OTHER LV EXCLUDING LV FOR ALARM SYSTEM, |
| | IT MAY BE INCLUDED ON THESE PLANS. (IE) |
| | SOUND LV, ETC. IF NOT SHOWN ON THESE |
| | PLANS, SEPARATE PLANS AND PERMIT WILL |
| | BE REQUIRED. IF SHOWN: IT WILL BE PART |
| | OF ELECTRICAL CONTRACTOR'S PERMIT WHICH |
| | IS SIGNED ON THIS PERMIT APPLICATION. |
| | **THIS IS ONLY A NOTE*** |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |