Plan Review Notes
Plan Review Notes For Permit 04070860
Permit Number 04070860
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-22 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 PLEASE INCLUDE ALL LICENSE #'S AND
 PRINTED NAMES AS REQUIRED PER ABOVE.
 PLEASE SEE FS 481.219 FOR REQUIRED LICEN
 -SE # MISSING.
 PLEASE ALSO SEE FS 481.221, MUST CONTAIN
 SIGNATURE. PLEASE SEE THAT PLANS APPEAR
 TO BE INITIALED AT THIS TIME. IF THIS
 IS ACTUAL "LEGAL" SIGNATURE, PLEASE
 PROVIDE A SIGNED,SEALED AND NOTARIZED
 LETTER STATING IT IS YOUR LEGAL SIG.
 WE WILL PLACE IN OUR SIGNATURE FILE FOR
 FUTURE REFERENCE .
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE LABEL PANELS AND LABEL
 PANELS ON PLANS. MULTIPLE PANELS ARE
 SHOWN AS BEING LEFTSIDE AND OR RIGHTSIDE
  
 4)NOTE: PLEASE SEE RISER INDICATE A
 PANEL FOR GEN PANEL, YET THERE IS NO
 PANEL SCHEDULE FOR THIS. PLEASE ALSO
 IDENTIFY ON PLANS.
 215.5
  
 5) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC.
  
 6) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 SOME ARE REDLINED ON PLANS.
  
 8) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 SOME AREA REDLINED ON PLANS.
  
 9 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OOF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
  
 10)NOTE: PLEASE INDICATE ALL A/C UNITS
 ON PLANS AND DISCONNECTS PER 440.11
  
 11)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 12)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 RECESSED FIX MAY ONLY BE FIGURED IN
 GENERAL LT IF LTS ARE MIN FOR EGRESS/
 GEN LT.
  
 13)NOTE: PLEASE CORRELATE AND LABEL
 A/C UNTIS ON PANEL SCHEDULE(S).
 PLEASE SEE A COUPLE SHOWN AS SAME ??
  
 14)NOTE: PLEASE SEE 424.3B FOR MIN OVER-
 -CURRENT PROTECTION TO BE 125%.
  
 15)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN
 ON PANEL SCHEDULE BUT GFI RECEPT NOT
 LOCATED OR INDICATED ON PLANS?680
 IS THIS MASTER BATH?
  
 16)NOTE: PLEASE SEE SOME A/C UNITS LOADS
 ARE SHOWN AS 20A'S AND OCP IS 20A'S,
 PLEASE SEE LOADING OF BRKR AT 80%?
 PLEASE ALSO VERIFY AHU #4 SHOWN AS 2P20A
 IS THERE NO HEAT FOR THIS UNIT?
 PLEASE CORRELATE TOTAL A/C KW IN LOAD
 CALCULATIONS AND WHAT IS INDICATED ON
 PANELS.
 215.5
 PLEASE SEE LOAD SHOWN FOR 15KW UNIT?
 PLEASE VERIFY THIS?
  
 17)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 -S ON PLANS.
  
 18)NOTE: PLEASE SEE PLANS INDICATED 3
 GDO'S ON RIGHT-SIDE HOWEVER ONLY TWO
 ARE INDICATED ON PANEL SCHEDULE? PLEASE
 VERIFY IF THESE ARE SHARED.
  
 19)NOTE: PLEASE ALSO SEE THERE APPEARS
 TO BE DEDICATED GOLF CART CHARGER RECEPT
 -S ON GARAGE WALLS, YET THESE ARE NOT
 INDICATED ON PANEL SCHEDULES?
 PLEASE VERIFY. 215.5
  
 20)NOTE: PLEASE SEE 210.52H FOR RECEPTS
 REQUIRED IN HALLS/HALL AREAS 10' OR MORE
  
 21)NOTE: PLEASE VERIFY WASH/DRYER SHOWN
 ON SECOND FLOOR APPEARS TO BE A SINGLE
 STACKABLE UNIT? PANEL SCHEDULE INDICATE
 UNITS AS BEING SEPARATE?
  
 22)NOTE: PLEASE SEE 210.52C1, APPEARS TO
 HAVE ONE RECEPT MISSING FOR KITCHEN
 COUNTERSPACE.
  
 23)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND STAMP-
 -ING. ONE SET OF OLD MAY BE SUBMITTED
 FOR REFERENCE ONLY.
  
 24)NOTE: PLEASE SEE THERE IS NO SYMBOL
 SCHEDULE/LIST SHOWN.
  
 *** NOTE***
 PLEASE SEE NO OTHER LV IS SHOWN ON PLANS
 ONLY CATV AND PHONE AT THIS TIME.
 PLEASE KNOW IF THERE IS GOING TO BE ANY
 OTHER LV EXCLUDING LV FOR ALARM SYSTEM,
 IT MAY BE INCLUDED ON THESE PLANS. (IE)
 SOUND LV, ETC. IF NOT SHOWN ON THESE
 PLANS, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED. IF SHOWN: IT WILL BE PART
 OF ELECTRICAL CONTRACTOR'S PERMIT WHICH
 IS SIGNED ON THIS PERMIT APPLICATION.
 **THIS IS ONLY A NOTE***
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved