| Plan Review Notes For Permit 04070846 |
| Permit Number |
04070846 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-11-17 00:00:00 | ******** UNSAT 3RD REVIEW ******** | | | | | | 1)NOTE: PLEASE SEE SAME NOTES FROM TWO | | | PREVIOUS REVIEWS. | | | LOAD CALCAULTIONS ETC HAVE STILL NOT | | | BEEN SUBMITTED.?? 215.5 | | | SUBMIT SPECS FOR HEAT PUMP SHOWING A | | | LISTING FROM A NRTL. | | | | | | 2)NOTE: PLEASE SEE RISER NOW SHOWS A NEW | | | FEED FROM EXSITNG PANEL. PLEASE SEE | | | MISSING EQUIPMENT GROUNDING CONDUCTOR. | | | 250.24,250.122 | | | | | | 3)NOTE: ENGINEER MUST ALSO DATE PLANS | | | WHEN SIGNING. MAY NOT BE A | | | PRINTED/STAMPED. FS 471.025 | | | | | | | | | 4)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B) WHICH IS ATTACHED WITH | | | RESPECT TO DESIGN PROFESSIONAL. | | | THIS IS ONLY A NOTICE GIVEN AT THIS | | | TIME. | | | | | | PLEASE SEE FIVE SETS OF PLANS ARE BEING | | | SUBMITTED. ONLY TWO IS NEEDED AND THREE | | | MAY BE SUBMITTED. ONLY THREE WILL BE | | | STAMPED UPON COMPLETETION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|