Plan Review Notes For Permit 04070846
Permit Number 04070846
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-02 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) NO VACUUM LINE SHOWN ON THE POOL LAY-
 OUT. THIS IS CALLED OUT ON POOL SPECIFI-
 CATIONS. PLEASE CORRELATE LAYOUT & SPECS
  
 REVIEW BY KEN STEVENS