| 2004-10-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) A SANITARY & A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM ARE REQUIRED SHOWING ALL |
| | PIPE SIZES ECT. SECTION 104.3.1.1. |
| | 2) MINIMUM SIZE DRAINAGE PIPE FOR SANT. |
| | OF A SINK IS 1-1/2" - THERE ARE NO 1" |
| | SANT. FITTINGS, ONLY PRESSURE FITTINGS. |
| | 3) A GATE VALVE LOCATED ON THE DISCHARGE |
| | SIDE OF THE CHECK VALVE SHALL BE IN- |
| | STALLED IN THE PUMP DISCHARGE PIPING BE- |
| | TWEEN THE PUMP AND THE GRAVITY DRAINAGE |
| | SYSTEM. |
| | 4) VENT REQUIRED FOR PUMP TANK, EITHER A |
| | VENT THROUGH THE ROOF OR TIE INTO EXIST- |
| | ING VENT SYSTEM. |
| | 5) SUBMIT A DETAIL FOR THE WATER HEATER |
| | SHOWING THERMAL EXPANSION CONTROL, P/T |
| | RELIEF VALVER DISCHARGE, AND PAN DRAIN |
| | DISCHARGE (IF APPLICABLE), PER SECTIONS |
| | 607.3.2, 504.7.1, &504.8.1.2. |
| | 6) FAC 61G1-16.004(2) FIRM LICENSE NUM- |
| | BER, (CERTIFICATE OF AUTHORIZATION), IS |
| | REQUIRED ON THE TITLE BLOCK ON EACH |
| | SHEET. FS 481.2055. - FAC 61G1-16.004(6) |
| | PRINTED NAME OF PERSON SEALING THE DOCU- |
| | MENT REQUIRED. FS 481.2055 |
| | |