2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A SANITARY & A WATER RISER DIAGRAM IN
 ISOMETRIC FORM ARE REQUIRED SHOWING ALL
 PIPE SIZES ECT. SECTION 104.3.1.1.
 2) MINIMUM SIZE DRAINAGE PIPE FOR SANT.
 OF A SINK IS 1-1/2" - THERE ARE NO 1"
 SANT. FITTINGS, ONLY PRESSURE FITTINGS.
 3) A GATE VALVE LOCATED ON THE DISCHARGE
 SIDE OF THE CHECK VALVE SHALL BE IN-
 STALLED IN THE PUMP DISCHARGE PIPING BE-
 TWEEN THE PUMP AND THE GRAVITY DRAINAGE
 SYSTEM.
 4) VENT REQUIRED FOR PUMP TANK, EITHER A
 VENT THROUGH THE ROOF OR TIE INTO EXIST-
 ING VENT SYSTEM.
 5) SUBMIT A DETAIL FOR THE WATER HEATER
 SHOWING THERMAL EXPANSION CONTROL, P/T
 RELIEF VALVER DISCHARGE, AND PAN DRAIN
 DISCHARGE (IF APPLICABLE), PER SECTIONS
 607.3.2, 504.7.1, &504.8.1.2.
 6) FAC 61G1-16.004(2) FIRM LICENSE NUM-
 BER, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED ON THE TITLE BLOCK ON EACH
 SHEET. FS 481.2055. - FAC 61G1-16.004(6)
 PRINTED NAME OF PERSON SEALING THE DOCU-
 MENT REQUIRED. FS 481.2055
  