2004-07-27 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS CONTAIN A
 "RUBBER STAMP" FOR SIGNATURE OF ARCH.
 PLEASE SEE FS 481.221 , PLANS ARE
 REQUIRED TO HAVE AN ORIGINAL SIGNATURE.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCK FOR ARCH/ARCH FIRM.
 PLEASE ALSO SEE FS 481.219 FOR REQUIRED
 FIRM LICENSE #.
  
 3)NOTE: PLEASE SHOW MIN CIRCUITS FOR NEW
 ITEMS SHOWN ON PLANS. PLEASE CORRELATE
 CIRCUITS WITH PANEL SCHEDULE(S) TO BE
 SUBMITTED.
  
 4)NOTE: PLEASE SEE 210.62 FOR SHOW WIND-
 -OW RECEPTS.
  
 5)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE ONLY AND MAY BE REQUIRED
 BY ONE OR MORE PLAN REVIEWERS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  