Plan Review Notes
Plan Review Notes For Permit 04070798
Permit Number 04070798
Review Stop E
Sequence Number 4
Notes
Date Text
2005-10-20 00:00:00********** PROVISO/REVISION ***********
  
 1)NOTE: PLEASE CORRELATERISER DIAGRAM
 ALONG WITH PANEL SCHEDULES FOR GARAGE
 PANEL.
 PER OWNER, #1 AWG IS INSTALLED.
 PLEASE SEE OCP IN MM AND RISER TO MATCH,
 SHOWS 70A AND 60A.
 PLEASE SEE RISER INDICATES SUB PANEL ON
 2ND FLR, HOWEVER PANEL IS LOCATED ON
 FIRST FLR RM.
 PLEASE INDICATE UTILITY RM UNDER STAIRS
 AS ELECTRICAL ROOM/ NO STORAGE.
 240.24D,408.7, 215.5, 240.4,310.16
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 3)NOTE: PLEASE SEE MISSING SD LOCATED
 OUTSIDE MASTER BEDRM AT TOP OF STAIRS.
 THIS WAS REDLINED ON PREVIOUS PLANS.
 NFPA-72 8-1.4.1.6.2
  
 4)NOTE:PLEASE SEE MISSING GFI AT
 PENINSULAR. PER OWNER, THIS WILL BE IN
 CABINETS AND ONLY TO STUB OUT AT THIS
 TIME.
 210.52C3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND STAMPING BEFORE FINAL
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  