| Plan Review Notes For Permit 04070798 |
| Permit Number |
04070798 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-10-20 00:00:00 | ********** PROVISO/REVISION *********** | | | | | | 1)NOTE: PLEASE CORRELATERISER DIAGRAM | | | ALONG WITH PANEL SCHEDULES FOR GARAGE | | | PANEL. | | | PER OWNER, #1 AWG IS INSTALLED. | | | PLEASE SEE OCP IN MM AND RISER TO MATCH, | | | SHOWS 70A AND 60A. | | | PLEASE SEE RISER INDICATES SUB PANEL ON | | | 2ND FLR, HOWEVER PANEL IS LOCATED ON | | | FIRST FLR RM. | | | PLEASE INDICATE UTILITY RM UNDER STAIRS | | | AS ELECTRICAL ROOM/ NO STORAGE. | | | 240.24D,408.7, 215.5, 240.4,310.16 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52 | | | | | | 3)NOTE: PLEASE SEE MISSING SD LOCATED | | | OUTSIDE MASTER BEDRM AT TOP OF STAIRS. | | | THIS WAS REDLINED ON PREVIOUS PLANS. | | | NFPA-72 8-1.4.1.6.2 | | | | | | 4)NOTE:PLEASE SEE MISSING GFI AT | | | PENINSULAR. PER OWNER, THIS WILL BE IN | | | CABINETS AND ONLY TO STUB OUT AT THIS | | | TIME. | | | 210.52C3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND STAMPING BEFORE FINAL | | | ELECTRICAL INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|