Plan Review Notes
Plan Review Notes For Permit 04070798
Permit Number 04070798
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-02 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAMS.
 TWO SUBMITTED??
 PLEASE ALSO CORRELATE WITH PANEL SCHED-
 -ULES.
  
 2)NOTE: PLEASE SEE 310.16 FOR SIZING
 OF FEEDERS AND SEC'S. SHOWS 1/0'S FOR
 200A SERVICE? ETC.
  
 3)NOTE: PLEASE SEE 30A OCP FOR WASHER?
  
 4)NOTE: PLEASE SHOW LOCATION OF PANELS /
 SERVICE EQUIPMET ON PLANS.
  
 5)NOTE: PLEASE SEE 250.50 FOR REQUIRED
 CWP FOR GROUNDING ELECTRODE.
  
 6)NOTE: PLEASE SEE "NOTE" MENTIONS SD'S
 ATTACHED TO KITCHEN LT CIRCUIT.
 PLEASE SEE 210.12 2002 NEC SD'S ARE
 REQUIRED TO HAVE ARC FAULT PROTECTION.
  
 7)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS.
 THIS IS REQUIRED ON ALL SHEETS,WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 8)NOTE: PLEASE ALSO SEE PLANS MENTIONS
 BEDRM RECEPTS TO BE ARC FAULT PROT.
 PLEASE SEE 2002 NEC 210.12.
 LTS/FANS/RECEPT, SD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]