| 2004-08-02 00:00:00 | *********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAMS. |
| | TWO SUBMITTED?? |
| | PLEASE ALSO CORRELATE WITH PANEL SCHED- |
| | -ULES. |
| | |
| | 2)NOTE: PLEASE SEE 310.16 FOR SIZING |
| | OF FEEDERS AND SEC'S. SHOWS 1/0'S FOR |
| | 200A SERVICE? ETC. |
| | |
| | 3)NOTE: PLEASE SEE 30A OCP FOR WASHER? |
| | |
| | 4)NOTE: PLEASE SHOW LOCATION OF PANELS / |
| | SERVICE EQUIPMET ON PLANS. |
| | |
| | 5)NOTE: PLEASE SEE 250.50 FOR REQUIRED |
| | CWP FOR GROUNDING ELECTRODE. |
| | |
| | 6)NOTE: PLEASE SEE "NOTE" MENTIONS SD'S |
| | ATTACHED TO KITCHEN LT CIRCUIT. |
| | PLEASE SEE 210.12 2002 NEC SD'S ARE |
| | REQUIRED TO HAVE ARC FAULT PROTECTION. |
| | |
| | 7)NOTE: PLEASE SEE FBC 104.2.1, PLANS |
| | ARE REQUIRED TO HAVE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS. |
| | THIS IS REQUIRED ON ALL SHEETS,WHEATHER |
| | OR NOT COMMENT IS MADE BY OTHER REVIEW- |
| | -ERS. |
| | |
| | 8)NOTE: PLEASE ALSO SEE PLANS MENTIONS |
| | BEDRM RECEPTS TO BE ARC FAULT PROT. |
| | PLEASE SEE 2002 NEC 210.12. |
| | LTS/FANS/RECEPT, SD. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |