| Plan Review Notes For Permit 04070757 |
| Permit Number |
04070757 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-04 00:00:00 | ***********DENIED*********************** | | | 1) UNDER THE SEQUENCE OF OPERATIONS THE | | | DUCT DETECTORS SHALL INITIATE AN "ALARM" | | | CONDITION IN THE THE BUILDING NOT A | | | SUPERVISORY. | | | | | | NATE MCCRAY, CAPTAIN | | | 835-2910 OR 805-6722 |
|