| Plan Review Notes For Permit 04070744 |
| Permit Number |
04070744 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | A) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | 1) BATH #2 LAV SHOWN AS CONNECTING BE- | | | LOW THE SLAB. THIS SHALL BE CONNECTED TO | | | A STACK ABOVE THE SLAB. LAV NOT VENTED | | | SECTION 901.2.1 | | | 2) BATH #2 W/C SHALL NOT BE TRAPPED ON | | | THE ROUGH AS IT HAS AN INTEGERAL TRAP IN | | | THE FIXTURE. SECTION 1002.1 | | | 3) NO HORIZONTAL DRY VENTS. SEC 905.3 | | | IN BATHS #2 AND MASTER BATH. | | | 4) WASH MACHINE REQUIRES A STANDPIPE A | | | MINIMUM OF 2', AND A CLEANOUT MINIMUM OF | | | 4' ABOVE THE FLOOR. SECTIONS 1002.1, | | | 802.4, AND 708.10. | | | 5) MASTER BATH W/C ON DIFFERENT WALL | | | THAN TUB AND LAVS. TWO LAVS SHOWN ON THE | | | FLOOR PLAN BUT ONLY ONE SHOWN ON RISER | | | DIAGRAM. SECTION 104.2.1 | | | 6) SAME NOTE AS #2, NO DOUBLE TRAPING | | | OF THE W/C. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|