| 2004-09-20 00:00:00 | ******** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | IT IS NOTED THE AVAILABLE FAULT CURRENT |
| | IS SHOWN FROM FPL. HOWEVER PLEASE INDI- |
| | -CATE ACTUAL AIC RATING OF EQUIPMENT. |
| | |
| | 2)NOTE: IF MAIN DISC IS INSTALLED OUT- |
| | -SIDE INFRONT OF PANEL, THEN AN EQUIP- |
| | -MENT GROUNDING CONDUCTOR IS REQUIRED. |
| | 250.24,250.110 |
| | |
| | 3)NOTE: PLEASE SEE 110.26 FOR CLEARENCE |
| | INFRONT OF ELECTRICAL PANEL. |
| | PLANS SHOW A WASHER/DRYER. |
| | |
| | 4)NOTE: PLEASE SEE BATHRM. PLEASE SEE |
| | 210.52D WHICH REQUIRES A GFI RECEPT |
| | W/IN 3' OF SINK/EDGE. |
| | |
| | 5)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| | REQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF PERSON RESPONSIBLE FOR PLANS. |
| | REQUIRED FOR ALL, WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWS |
| | |
| | 6)NOTE: PLEASE CLARIFY WHATS APPEARS TO |
| | BE A PENINSULAR AREA FOR KITCHEN |
| | COUNTERSPACE. 210.52C2 |
| | |
| | 7)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. |
| | |
| | 8 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 2002 NEC |
| | IT IS NOTED ABOVE PANEL SCHEDULE. |
| | |
| | 9)NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONAL. |
| | SEE COPY ATTACHED. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |