Plan Review Notes
Plan Review Notes For Permit 04070744
Permit Number 04070744
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-20 00:00:00******** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IT IS NOTED THE AVAILABLE FAULT CURRENT
 IS SHOWN FROM FPL. HOWEVER PLEASE INDI-
 -CATE ACTUAL AIC RATING OF EQUIPMENT.
  
 2)NOTE: IF MAIN DISC IS INSTALLED OUT-
 -SIDE INFRONT OF PANEL, THEN AN EQUIP-
 -MENT GROUNDING CONDUCTOR IS REQUIRED.
 250.24,250.110
  
 3)NOTE: PLEASE SEE 110.26 FOR CLEARENCE
 INFRONT OF ELECTRICAL PANEL.
 PLANS SHOW A WASHER/DRYER.
  
 4)NOTE: PLEASE SEE BATHRM. PLEASE SEE
 210.52D WHICH REQUIRES A GFI RECEPT
 W/IN 3' OF SINK/EDGE.
  
 5)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF PERSON RESPONSIBLE FOR PLANS.
 REQUIRED FOR ALL, WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWS
  
 6)NOTE: PLEASE CLARIFY WHATS APPEARS TO
 BE A PENINSULAR AREA FOR KITCHEN
 COUNTERSPACE. 210.52C2
  
 7)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING.
  
 8 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
 IT IS NOTED ABOVE PANEL SCHEDULE.
  
 9)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL.
 SEE COPY ATTACHED.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]