| Plan Review Notes For Permit 04070725 |
| Permit Number |
04070725 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-25 00:00:00 | 1) A MINIMUM CLEAR AND UNOBSTRUCTED | | | WIDTH OF 20' MUST BE PROVIDED FOR | | | EMERGENCY VEHICLES. PLEASE INDICATE HOW | | | THE FIRE DEPARTMENT CONNECTION WILL BE | | | ACCESSED THROUGH THE STUDENT DROP OFF | | | AND PLAY AREA. | | | | | | 2) THE FDC SHALL BE LOCATED AT A | | | DISTANCE NOT FURTHER THAN 150' FROM THE | | | CLOSEST FIRE HYDRANT. | | | | | | 3) PLEASE PROVIDE FURTHER DETAILS | | | REGARDING THE BACK FLOW PREVENTOR. | | | | | | 4) THE BACK FLOW PREVENTOR SHALL BE | | | SECURED WITH A CHAIN AND LOCK IN | | | ADDITION TO ELECTRONIC SUPERVISION. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|