Plan Review Notes
Plan Review Notes For Permit 04070719
Permit Number 04070719
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-30 00:00:00ELECRTICAL PERMIT WILL BE APPLIED FOR
 SEPERATELY OK PR L MARTINEZ/DRUNNELS NFL
2004-07-27 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON AND FOR TITLE BLOCK.
 FAC 61G15-23.002
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 2)NOTE: PLEASE CLARIFY SERVICE?
 SEEMS TO SHOW AND EXSITING SERVICE
 GOING TO "TELCO" PANEL AND NEW SERVICE
 FOR NEW EQUIPMENT?
 THESE BOTH SEEM TO CROSS OVER FROM EACH
 SERVICE ON RISER DIAGRAM??
  
 3)NOTE: PLEASE SEE 250.24,250.6, AN
 EQUIPMENT GROUNDING CONDUCTOR MAY NOT
 BE INSTALLED UNTIL AFTER THE FIRST MEANS
 OF DISC.
  
 4)NOTE: PLEASE SEE FBC 104.6.5, VALUE
 ON APPLICATION IS TO INCLUDE ALL LABOR
 AND MATERIALS, EVEN IF ANY OR ALL IS
 OWNER SUPPLIED.
 ALL EQUIPMENT ETC IS TO BE INCLUDED.
  
 5)NOTE: PLEASE SEE PLANS ARE ONLY IN FOR
 PLAN REVIEW AND NOT FOR PERMIT.
  
 6)NOTE: PLEASE SEE ZONING NOTES.
 PLANS ARE TO PLACED ON HOLD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved