 REFERENCE: FBC-2001 424 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 2) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 3) SHT 1 SPA APPERTENANCES INDICATES 5
 THERAPY INLETS, BUT SPA PIPING PLANS
 SHOW 8 THERAPY INLETS. PLEASE CLARIFY/
 CORRELATE PLANS.
 4) REVISIONS FOR BLDG. PLANS SHALL BE
 SUBMITTED SEPARATELY UNDER BLDG. PERMIT
 NUMBER AS A REVISION.
  